The Use of Heat Pumps to Induce Airflow on Hot Days in Otherwise Passive Ventilation Systems: A Zonal Modelling Approach

Stephen Gage, Phil Ayres, James Axon

Publications: Contribution to journalJournal articleResearchpeer-review

Abstract

This paper presents results from a wider study into pro viding displacement ventilation in urban areas by taking air into buildings from the top without the use of fans. Results from large scale experimental work are given. These results indicate that ventilation airflows can be induced using gravity chillers and heaters in conditions where this type of installation would otherwise fail. The paper also describes initial experiments undertaken to see how far the same equipment can be used for heat recovery. One test installation was modelled using a pro prietary zonal model. A further zonal model was created to compare an assisted gravity system with a partially fan-driven system. This system failed on numerous occa sions during a hot summer. However, fans are shown to be advantageous in winter heat recovery. A hybrid sys tem is suggested for use under UK conditions.
Original languageEnglish
JournalIndoor and Built Environment
Volume9
Issue number3-4
Pages (from-to)127-142
Number of pages15
ISSN1420-326X
DOIs
Publication statusPublished - 2000
Externally publishedYes

Keywords

  • Heat pumps
  • Urban air pollution
  • Top-down ventilation

Artistic research

  • No